GREEN EMERGENCY POWER PACK
SPECIFICATIONS FOR MODEL: GEPP118 & GEPP136
 
PARAMETERS
UNIT
GEPP118
GEPP136
Lamp Type
-
18W
36W
Rated Input Voltage
(Vac)
240
240
Input Voltage Range
(Vac)
216 - 264
216 - 264
Input Frequency
(Hz)
50/60
50/60
Operation Frequency
(kHz)
32
23
No Lamp Operation Frequency
(kHz)
55
28
Maximum Input Current
(A)
0.03
0.03
Starting Time
(sec)
< 0.3
< 0.3
Maximum Ambient Temperature
(ta°C)
+55
+55
Operating Temperature
(tc°C)
+10 to +40
+10 to +40
DC Ballast Storage Temperature
(C)
0 to +50
0 to +50
Battery
-
NiCd 6.0V 4.5Ah
NiCd 6.0V 4.5Ah
Ballast Lumen Factor
(%)
18
15
Battery Discharge Current
(A)
1.45
1.30
Duration
(h)
3
3
Minimum Recharge Time
(h)
24
24
DC Ballast Weight
(g)
350
350
DC Ballast Dimensions
(mm)
252(L) x 42(W) x 35(H)
252(L) x 42(W) x 35(H)

* Technical data subject to change without notice.

Attention:
•  Use battery according to specifications.
•  The batteries should be charged for at least 48 hours before using the emergency system.
•  To achieve best performance, the batteries should be replaced every 4 years.
•  Place the battery pack as far as possible from sources of heat (eg: the ballast) as high temperature will reduce battery life.
•  Battery and GEPP will be damaged if both terminals of battery shorted.

DIMENSIONS: (MM)



WIRING DIAGRAM: GEPP with Micatron HGB series Electronic Ballasts
Note1: When using GEPP 118, replace the electronic ballast to 18 watts ballast accordingly, (eg: HGB14098 - HGB12098).
Note2: please refer to the factory for connection with electronic ballasts by opther manufacturers.












WIRING DIAGRAM: GEPP with Conventional Ballasts